+34 93 574 30 84
  • Facebook
  • Twitter
  • LinkedIn
  • Instagram
  • YouTube
  • Español
  • Français
  • English

CUADROS-RESIDUAL

Electrical panels for wastewater

LOGICPANEL SEWAGEAPPLICATIONS
  • Control panel for waster water lifting station with 1 or 2 pumps using electronic level probe instead of conventional level switches.
  • The control panel includes the level probe that is suitable for working with wastewater and allows installation of a conventional level switch as an emergency system.
  • Also includes a configurable remote contact.
  • Easy and accurate configuration thanks to the control panel that allows to adjust the start, stop and alarm levels as well as the power consumption of the pumps.
  • Its display allows for real-time visualization of the water level and power consumption of the pumps.
  • Pumps alternate at each start or forced alternation by time in case of continuous operation.
  • It also includes anti-lock protection: if the pumps remain inactive for 24 consecutive hours, the device will start the pump for 5 seconds to prevent its blocking by inactivity.
TECHNICAL CHARACTERISTICS
  • Supply Voltage: M2HP (c.2753): 1 ~ 115 / 230 Vac ±10% - T4HP (c.2754): 3 ~ 400 Vac ±10%
  • Frequency: M2HP (c.2753): 50 / 60 Hz - T4HP (c.2754): 50 / 60 Hz
  • Max. intensity of pumps: M2HP (c.2753): 10 A - T4HP (c.2754): 8 A
  • Protection degree: M2HP (c.2753): IP-65 - T4HP (c.2754): IP-65
  • Max. temperature: M2HP (c.2753): 60ºC - T4HP (c.2754): 60ºC
  • Dimensions: M2HP (c.2753): 205 x 170 x 53 mm - T4HP (c.2754): 250 x 350 x 150 mm
  • Output level probe: M2HP (c.2753): 4-20 mA - T4HP (c.2754: 4-20 mA
  • Level probe cable length: M2HP (c.2753): 5 m. - T4HP (c.2754): 5 m.
  • Min. reading height: M2HP (c.2753): 5 cm - T4HP (c.2754): 5 cm
  • Max. reading height: M2HP (c.2753): 5 m - T4HP (c.2754): 5 m
  • Weitght: M2HP (c.2753):0,5 kg - T4HP (c.2754): 2,8 kg
  • Certifications: M2HP (c.2753): CE - TUV - T4HP (c.2754): CE - TUV
ELECTRIC CONTROL PANELS FOR WASTE WATERTECHNICAL CHARACTERISTICS
  • Supply voltage: single-phase 1~230V - three-phase 3~400V - three-phase 3~230V (230V control circuit).
  • Direct Starter (DS) up to 5,5CV (4kW) and Star-Delta (SD) from 7,5CV (5,5kW).
  • Plastic box up to 5,5CV (4kW) and metallic box from 7,5CV (5,5kW).
  • Pump/s protection by circuit breaker.
  • 3 positions selector switch MAN-O-AUT (manual - OFF - automatic) for every pump.
  • Pump-on and themal switch pilots.
  • Pilot and acoustic alarm for overlevel.
  • Pumps alternation sequence by means of a relay.
  • Operation by level switches (single panel: 1 or 3 level switches / double panel: 4 level switches).
  • On request it can be supplied with ATEX-EX intrinsic secutity barriers.


Valid HTML5 ¡CSS Válido!